Every three years, the National Electrical Code® (NEC®) is revised and expanded. Initially the NFPA® received 4,006 public suggestions for changes, which resulted in 1,805 first revisions. There were 1,956 public comments submitted in response to these 1,805 first revisions, resulting in 900 second revisions. Changes included editorial clarification, expanded requirements, new requirements, deleted requirements, and the relocation of other requirements.
What to Expect
In this course the student will be presented an overview of the most significant changes found in the 2023 NEC. This is part 1 of a series of courses covering the changes and will progress through each chapter and its articles presenting the many important changes. The changes will be underlined for easy recognition and a short synopsis of the reason for the change is presented as well.
Disclaimer
Although every effort has been made to the accuracy of the material presented, by no means shall the student use or substitute this material for official 2023 NEC. Additionally, Ezekiel Enterprises, LLC shall not be liable for any special, incidental, consequential, or exemplary damages resulting, in whole or in part, from the reader’s uses of or reliance upon this material.
Revision – 500.4
Documentation
■ What Changed: Additional language added in Section 500.4 to assist the authority having jurisdiction (AHJ) for requirements on documentation for hazardous (classified) locations. The parent text of 500.4 was revised to require that the documentation provided includes an area classification drawing. The change will create a consistent method of documenting hazardous (classified) locations and clearly indicate the boundaries between the classified areas and unclassified areas.
■ Its Effect: This new language allows the AHJ to require the designers to provide additional information on the plans for the installations and inspections in the field to verify code compliance with the NEC. This new language will assist the electrical plans examiner, inspector, and installer to verify that the installation meets Code requirements for all hazardous (classified) locations.
Revision – 500.5(D)(1)(a)
Combustible Fibers/Flyings
■ What Changed: The previous Code language at 500.5(D)(1)(a) has been completely reworded to align with the new definition for combustible fibers/flyings and the edits for combustible dust.
■ Its Effect: The new language and definitions will help the industry determine the type of hazardous (classified) locations that exist. The consistency in language for all the NFPA standards for the new definitions will assist all electrical professionals who design, install, and inspect in these environments.
Revision – 500.8(D)(2) and (3)
Equipment, Temperature, Class II and Class III
■ What Changed: The previous language for 500.8(D)(2) and (3) that involve Class II and Class III temperature has been edited and revised to align with the new definition for combustible fibers/flyings.
■ Its Effect: The edits to 500.8(D)(2) and (D)(3) and the new definition will help the industry to determine the type of equipment permitted in these locations. This change provides consistency in language and requirements for all electrical professionals who design, install, and inspect.
New – 505.9(C) Chapter 9 Table 13
Equipment Suitable for Hazardous (Classified) Locations
■ What Changed: A new Table 13 was created in Chapter 9 entitled Equipment Suitable for Hazardous (Classified) Locations. The text was deleted at 505.9(C)(2)(4) referencing Table 505.9(C)(2)(4) with new text added to reference Chapter 9 Table 13. The new Table 13 in Chapter 9 provides a complete list of the types of protection for hazardous (classified) locations and improves the readability of 505.9(C)(2) (4).
■ Its Effect: This new table will assist the electrical industry by providing an improved list of equipment suitable for various locations. The new table and revisions will assist the designer, contractors, and the AHJ in verifying compliance with the Code and the manufacturer’s listing of the equipment installed in a hazardous (classified) location for both zone and other classified locations.
New – Article 512
Cannabis Oil Equipment and Cannabis Oil Systems Using Flammable Materials
■ What Changed: New Article 512 was created to cover cannabis oil extraction equipment, booths, postprocessing equipment, and systems using flammable materials in commercial and industrial facilities. This is a new and expanding industry, and Article 512 is intended to address the hazards associated with the extraction of cannabis oil. This is in response to concerns raised by authorities having jurisdiction (AHJ) and other industry members regarding fire and explosion hazards associated with equipment used to process and extract plant oils from cannabis.
■ Its Effect: The cannabis industry has its own unique set of issues that require designers, contractors, and inspectors to become familiar with the new extraction and processing technologies. Flammable solvents such as butane, pentane, hexane, propane, and ethanol can be released during the processing and extraction of plant oils. This may also include high temperatures and high pressures, which increase the risk of fire and explosion.
Revision – 515.10
Special Equipment – Motor Fuel Dispensers
■ What Changed: The title of Section 515.10 was changed from “Gasoline Dispensers” to “Motor Fuel Dispensers.” This change was to assist the industry regarding code enforcement for all types of fuel dispensers, regardless of fuel type.
■ Its Effect: The revisions will help the industry understand that this requirement applies to all flammable liquids and liquified flammable gases. This will assist the electrical industry concerning the design, installation, interpretation, and enforcement of the Code.
Revision – Article 517
Health Care Facilities
■ What Changed: With the edition of the 2023 NEC, the phased approach has been completed of changing the references found in Article 517 for health care facilities from critical, general, basic, and support spaces to Category 1, 2, 3, and 4 Spaces.
■ Its Effect: This will allow for harmony between the two documents with fewer conflicts between designers and installers/inspectors. Consistent use of the terminology related to patient care and support spaces will bring better useability to the Code. Many users of the NEC are also users of NFPA 99, therefore if the two documents are using the same terminology, the user can better understand the requirements.
New – 517.6
Patient Care-Related Electrical Equipment
■ What Changed: It has been determined that the reconditioning requirements found elsewhere in the Code do not apply to patient care-related electrical equipment. Patient care-related electrical equipment is different from the other electrical equipment as it will be reconditioned or recertified in accordance with U.S. Federal Food, Drug, and Cosmetic Act (FDCA) when relocated. Health care facilities have used reconditioned equipment for many years without any record of failure, and it is imperative they maintain the ability to do so.
■ Its Effect: This clarification is beneficial to the electrical professional, so they are aware that marking and labeling requirements found at 110.21(A)(2) and other restrictions on the use of reconditioned equipment will not apply to electrical equipment used in patient care-related activities.
Relocation / Revision – 517.13
Equipment Grounding Conductor for Receptacles and Fixed Electrical Equipment in Patient Care Spaces
■ What Changed: Section 517.13 was revised for clarity by relocating former Exception No. 2 to follow the opening paragraph and by stating wiring “serving” patient care spaces. The change was necessary to clarify the connection of the equipment grounding conductor for receptacles and fixed electrical equipment in patient care spaces.
■ Its Effect: The change will provide a clear understanding of the application of the equipment grounding conductor connection requirements for branch circuits serving patient care spaces.
New – 517.22
Demand Factors
■ What Changed: It has been determined that the use of demand factors is acceptable and permitted for general-purpose receptacle loads in Category 1, 2, 3, and 4 patient care spaces. Without the ability to apply demand factors to the receptacle load calculations required by Article 220, unnecessarily large feeders to branch circuit panelboards supplying patient care areas resulted. To provide relief to this situation, Section 517.22 was added to provide a reference to Section 220.48, Receptacle Loads – Health Care Facilities,
■ Its Effect: The permitted use of demand factors for calculating loads in patient care areas will provide relief to electrical professionals when sizing feeders to branch circuit panelboards supplying those areas.
Revision – 517.30
Sources of Power
■ What Changed: Revisions were made for consistent use of terminology, to clarify the types of sources of power, and to recognize energy storage systems and health care microgrids in Section 517.30. Revisions were also made to clarify that the essential electrical system (ESS) must have two independent sources: one on-site source (or set of sources) that must be sized to supply the entire EES and another source, permitted to be on-site or off-site, that must also supply the entire EES. Additional sources other than the first two independent sources can be sized for the intended load.
■ Its Effect: The electrical professional will have a clearer understanding of the Energy Storage System (EES) power source requirements and also become aware of the addition of two new sources of power. The newly added sources of power have been proven to be reliable for all types of health care type occupancies along with already accepted types of occupancies.
Revision – 517 Part V
Diagnostic Imaging and Treatment Equipment
■ What Changed: The title and applicable text in Article 517 have been changed from “X-Ray Installations” to “Diagnostic Imagining and Treatment Equipment.” The previous language did not adequately distinguish between x-ray equipment and other modalities for diagnostic imagining. More and more non-x-ray diagnostic equipment is becoming the industry norm, so the NEC needed to better define these needs.
■ Its Effect: The title and applicable text were revised to adequately address current industry practices and equipment encountered in these locations. This will make the useability of the NEC better for the user.
Revision – 518.2
General Classification. (A) Examples.
■ What Changed: Casinos and gaming facilities are now included in the list of assembly occupancy examples.
■ Its Effect: If there was any confusion within the electrical professional community, this addition of these two locations clarifies that Article 518 applies to casinos and gaming facilities. In the past, there has been some confusion of whether or not casinos are considered assembly occupancies in the electrical community as well as the building community.
Revision – 518.4
Wiring Methods
■ What Changed: Section 518.4(A) and the Exception were revised into a list format, and two titled subdivisions and content were added to clarify that Power over Ethernet (PoE) is included. Two titled subdivisions were added, providing clarity and usability. Previously, the reference to Class 2 and 3 circuits in Article 725 was specific to remote control and signaling circuits. Section 518.4(B)(4), Class 2 circuits that transmit power, data, or both to a powered device, was added, making it clear that Power over Ethernet
(PoE) is permitted as a fixed wiring method for that specific application.
■ Its Effect: The reformat of Section 518.4(A) adds clarity and usability to the document. The electrical professional will find this more user-friendly and easier to reference. Changes in technology present changes in the Code or the Code becomes outdated. Not addressing new technologies does not give the Code user any direction. Can also prevent a conflict between inspectors and installers.
Revision – 518.5
Supply
■ What Changed: The section concerning assembly occupancies was reorganized for clarity and revised, including requirements for commercial appliance outlet centers and panelboard orientation. The reorganizing into a list format with titled subdivisions was necessary, as previously, there were several requirements in a single paragraph. In addition, revisions to specifically reference commercial outlet appliance centers that have unique features such as a panelboard in a face-up position were added. Because the general requirements for panelboard orientation in 408.43 do not permit mounting of panelboards in a face-up position, it was necessary to permit the orientation for listed commercial appliance outlet centers designed for in-floor mounting.
■ Its Effect: The reorganization of this section provides clarity for the electrical professional while recognizing the use of specific equipment. This should enhance the useability of the Code resulting in fewer conflicts between the installer and the AHJ.
Revision / Reorganization – Article 530
Motion Picture and Television Studios and Remote Locations
■ What Changed: Article 530 was completely reorganized for clarity and rewritten to remove old technologies and to include dominant and emerging new technologies. The article’s rewrite was the result of the work of a task group with a broad representation from motion picture producers, labor, supply chain, and users. The scope of the article was revised to acknowledge current safe work practices by stating that the requirements of the article apply to motion picture and television studios in facilities and locations staffed by qualified persons. “Locations” was added to the areas covered by the article as production no longer just occurs only in major centers such as Hollywood and New York. It can occur anywhere in the country. The term “location” is defined in Article 100 as a place outside a motion picture studio where a production is filmed or recorded.
■ Its Effect: The changes in Article 530 will provide additional clarity for AHJs and other electrical professionals in locations where motion picture or television work and production was not the norm.
New – 547.26
Physical Protection (Agricultural Buildings)
■ What Changed: A new Section 547.26, Physical Protection, was added to the 2023 NEC as it was determined that nonmetallic cables will be prohibited from being concealed within walls and above ceilings of buildings that are contiguous with or physically adjoin livestock confinement areas. Rodents and other pests have caused damage to wiring systems such as nonmetallic sheathed cables. Therefore, the use of this wiring method concealed in walls and above ceilings is no longer allowed. There is also a requirement that protection is to be provided for all types of electrical wiring that is subject to physical damage.
■ Its Effect: The installer and inspector should be aware that the use of a non-metallic sheathed cable to be concealed in walls or above ceilings in an agricultural building is prohibited.
New – 547.44
Equipotential Planes and Bonding of Equipotential Planes
■ What Changed: New Section 547.44(A) and (B) were added to clarify the indoor and outdoor locations requiring equipotential planes and specified the bonding locations of equipotential planes in. It was determined the previous language needed clarification as to where to bond the equipotential plane(s). The language now addresses locations where the equipotential plane can be connected for agricultural environments. Bonding should take place to the following items: a circuit equipment grounding conductor (EGC), any metal part connected to a circuit equipment grounding conductor, the grounding electrode conductor (GEC), any grounding electrode of the grounding electrode system (GEC), or the equipment-grounding terminal in a panelboard.
■ Its Effect: Electrical planes and their connections are mysterious to some electrical professionals. Agricultural environments are locations that some installers will never be working at and have specific requirements to ensure safety of livestock and individuals. Proper bonding of metal parts and structures will assure that voltage gradients do not exist, causing voltage to be felt by animals or individuals of these facilities. The electrical professional will need to be aware of these requirements and conditions and take appropriate steps to comply with these requirements.
Revision – 550.32
Service Equipment
■ What Changed: The electrical service disconnect can now be located within sight from the mobile home as opposed to 30 feet. The change from 30′ to 50′ (within sight) was an effort to be more consistent with other electrical disconnecting requirements. Specifically, with the changes in 230.85, this mobile home service disconnect could also serve as the emergency disconnect to eliminate the need for two disconnects on the exterior of the mobile home.
■ Its Effect: The service is now allowed to be installed in an accessible location outside of the mobile home and within sight from the mobile home it serves.
New – 551.3
Electrical Datum Plane Distances
■ What Changed: A new Section 551.3, Electrical Datum Plane Distances, was added. Initially, there was no requirement in the NEC to address RV parks located next to bodies of water. In addition, it was quickly realized that the change was necessary to clarify some of the inconsistencies related to all electrical equipment installations around bodies of water. With the changes to the definitions for “Electrical Datum Plane” and “Normal High-Water Level,” the inclusion of these requirements in Article 551 for recreational vehicles and recreational vehicle parks made sense.
■ Its Effect: This new information will clarify the requirements for the AHJ when applying electrical elevation requirements in an RV park located next to a body of water. The installer and AHJ will need to determine if the area will be subject to tidal fluctuations or not.
Revision – 551.40(D)
Loss of Ground Device
■ What Changed: Section 551.40(D) was changed to eliminate the need for a Reverse Polarity Device in a recreational vehicle. The “Loss of Ground” device would notify users of the recreational vehicle (RV) if a hazardous condition exists that may result in a “hot skin” (electrical current on the frame of the RV) condition.
■ Its Effect: This requirement will become effective January 1, 2026. The 2023 NEC language states that “each recreational vehicle shall have a listed grounding monitor between the feeder assembly connection and the transfer equipment or panelboard.” Manufacturers would be required to create a solution by providing a loss of ground device for the recreational vehicle. This change, in my opinion, wouldn’t impact the electrical contractor or installer.
Revision – 555.4
Location of Service Equipment
■ What Changed: Section 555.4 was modified to state that service for a marina or docking facility must be no closer than 1.5 m (5 ft) horizontally from the structure served and elevated to a distance of 12″ above the electrical datum plane. Section 555.4 previously only addresses the fact that the service for a marina or docking facility must be located on land adjacent to the structure served. The language was vague with regards to the minimum distance horizontally and also the height the service could be located above the electrical datum plane. Adding the distance for the service location and height above the electrical datum plane promotes electrical safety and enforceability. In addition, the new language will provide a correlation between similar requirements in Articles 682 and 555.
■ Its Effect: The impact on the electrical industry will be minimal. However, these specific measurements being added to this section will promote usability and consistency for both the AHJ enforcing the Code and the installer. These similar requirements already exist in Article 682 for other bodies of water.
Relocation – 555.6
Load Calculations for Service and Feeder Conductors
■ What Changed: Text relocated from Section 555.6 to 220.120 to better align with the “calculations” for services and feeders being located in Chapter 2.
■ Its Effect: The impact on the electrical industry will be minimal; however, these specific measurements being added to this section will promote usability and consistency for both the AHJ enforcing the Code and the installer. These similar requirements already exist in Article 682 for bodies of water. The effort to review and correlate similar requirements was necessary because the electrical safety concerns are the same.
New – 555.14
Equipotential Planes and Bonding of Equipotential Planes
■ What Changed: A new 555.14, Equipotential Planes and Bonding of Equipotential Planes, was added to Article 555. The new change will help in mitigating step and touch voltage where electrical equipment is located within 10 feet of the water’s edge and exceeding 250 volts to ground.
Also to better correlate with Article 682, equipotential planes were added in marina environments.
■ Its Effect: The impact on the industry will be minimal. Similar requirements already exist in Article 682 for bodies of water. The effort to review and correlate similar requirements was necessary because the electrical safety concerns are the same. The installer and AHJ will need to verify the presence of the equipotential plane or develop plans for the installation of one.
New – 555.15
Replacement of Equipment at Marinas, Boatyards, Floating Buildings, and Commercial and Noncommercial Docking Facilities
■ What Changed: Language has been added to a new Section 555.15 that mandates that “replacement” electrical equipment at docking facilities be installed to the current edition of the NEC. In addition, the new language will also allow the AHJ to inspect the existing electrical equipment for any damage. The damage found for existing equipment needs only to be repaired to the NEC edition for which it was originally installed.
■ Its Effect: With the new provision, if replacements are being done to electrical equipment, it will allow the AHJ to review the entire circuit. Realizing the entire circuit doesn’t have to meet the current NEC, my guess is that it will still add time and money to installations when the entire circuit is reviewed for damage. Money is a concern for existing marina owners. Figuring out which edition of the NEC that damaged electrical equipment was installed could also be problematic.
New – 555.35(E)
Leakage Current Measurement Device
■ What Changed: Language was added to 555.35(E) to recognize that the leakage current device is required to be listed by January 1, 2026. The language for leakage current devices was added to the 2020 NEC. Initially, the required leakage current testing device had no specific standard in place to build, test, or construct this metering equipment specific for a marina environment. So, by now requiring a “listed” Leakage Current Measurement Device for use in Marina Applications by January 1, 2026, will assure that the device complies with specific safety and performance requirements. Currently, UL 1399, The Outline of Investigation for Leakage Currently, Measurement Devices for use in Marina Applications, is under development to help the industry certify these devices.
■ Its Effect: The impact on the electrical industry will be minimal, however, UL 1399 product standard will standardize the testing equipment. The listed test device will allow the marina or facility operators to identify vessels that are leaking current to better mitigate any electrical hazard that could lead to a potential ESD event. The leakage current measurement device will be required to be provided by the marina owners when they have over three vessels supplied by shore power receptacles.
New – 555.36(C)
Emergency Electrical Disconnect
■ What Changed: Language has been added at a new subdivision 555.36(C) to mandate that an emergency disconnect be located within sight of a marina power outlet or enclosure that provides shore power to boats. The location of the emergency disconnect is critical, it needs to be located at each boat slip to be effective at having a chance to save the lives of electric shock drowning (ESD) victims and rescuers.
■ Its Effect: There are numerous documented incidents where an emergency disconnect could have saved lives from ESD. The electrical industry has embraced emergency disconnects in the NEC for many types of installations for maintenance reasons and people protection. The difficulty for the installer will be finding a location within sight of the marina power pedestal for the placement of the emergency disconnect that will be obvious to the boat owners.
New – 555.38
Luminaires
■ What Changed: In the 2020 NEC, Article 555 did not address luminaires. Section 555.38, Luminaires, was added to the 2023 NEC as a result. This section should help both installers and AHJs address electrically safe installations of luminaires at docking facilities to help reduce the incidents of electric shock drowning.
■ Its Effect: This information provides the installer and AHJ with clear guidelines to what types of luminaires can be installed either above or below the water level at a marina.
Revision – 590.4(F)
Lamp Protection
■ What Changed: Some existing text was removed concerning various socket styles at Section 590.4(F), and the words “metal guarded sockets” and “metal guard” were added. The previous language dates back to at least the 1990 edition of the NEC. The change in terminology from “grounded” to “equipment grounding conductor” in the 2020 NEC caused confusion. Some installations did not have an equipment grounding conductor as it was not needed. In many cases, the only two conductors available were the “hot” and the “neutral” conductor. This change requires the installation and use of an equipment grounding conductor to the metal guard when metal guarded lamp protection sockets are used.
■ Its Effect: This change will add clarity to the requirement and address newer lighting fixtures made out of plastic that do not require connection to the equipment grounding conductor.
New – 600.5(A)
Exception
■ What Changed: Two exceptions added for Section 600.5(A). Exception No. 1 was added, moving text that was originally in the last sentence of the main body of requirement. Exception No. 2 was added and allows time clocks and similar devices to be on the sign circuit. This was added to clarify the additional equipment required to power the sign circuit and may be included in the rating of the branch circuit. Signs are often controlled by time switches or photocontrols, both of which would be considered “loads.” Even photocontrols use a small amount of power, although it is typically less than 1 volt-amp. The proposed second exception permits the required branch circuit to also serve as the supply for a time switch or photocontrol, which is directly related to the control of the sign.
■ Its Effect: These changes will enhance the applicability and usability of the Code for the electrical professional. The relocation of the last sentence from the main body into Exception No. 1 will create a better separation between the mandatory rules. The addition of Exception No. 2 will clarify that photocells, timeclocks, and similar control devices are permitted to be on the same branch circuit as the sign.
Deletion – 600.35
Retrofit Kits
■ What Changed: Section 600.35 had redundant requirements removed, which are already covered in Chapters 1-4 of NEC.
■ Its Effect: Removing some of the requirements in 600.35 will require sign installers and other electrical professionals to be familiar with the other areas of the NEC that may apply to these electric signs and outline lighting installations.
New – 620.12(A)
Traveling Cables
■ What Changed: Class 2 communication conductor(s) were added for use with elevator traveling cables. This allows elevator communications conductors to be compatible with standard building wiring infrastructure and hardware. Class 2 cables are also allowed in the elevator hoistway and pit locations [see Article 620.21(A)(1)] and thus would not create any additional risk. Cables used for elevators as traveling cables for Class 2 or communications circuits to have current limit equal to or greater than the current required to power the powered Class 2 or communications device. The smallest size for the communication circuit is specified as a 24 AWG conductor.
■ Its Effect: This change allows the electrical professional to install a communication type limited power cable in the traveling cable and accommodates all communications and Class 2 applications including power over Ethernet (PoE). This should alleviate any confusion between the installer and the AHJ as to the requirements for this specific installation.
Revision – 620.22(A)
Car Light Receptacles, Auxiliary Lighting, and Ventilation
■ What Changed: Requirements in Section 620.22(A) were revised to specify permissible loads on the car light circuit.
■ Why it happened: Changes in equipment used in modern elevator cars have resulted in confusion about the permitted power source for these loads. This change clearly limits which loads may be powered by the car light circuit. Equipment now includes emergency responder radio coverage, air purification equipment, car emergency signing, and communication devices. The amperage for these new items is very small, with the risk of tripping the overcurrent protective device minimal. It will help the NEC align with the next edition of the ASME A17.1/CSA B44, Safety Code for Elevators and Escalators.
■ Its Effect: The revision at 620.22(A) will help the electrical professional with rapidly changing elevator technology and aid in accommodating modern technology and safety. It will also aid designers and installers in achieving Code compliance and simplify the work of AHJs in evaluating installations.
Revision – 620.36
Different Systems in One Raceway or Traveling Cable
■ What Changed: Shielded pair cables, coaxial cables, and communication cables complying with 800.179 are now specifically permitted in Section 620.36. There is a need for various cables for communications in modern elevator cars. The specific addition of coaxial and shielded pair cables will allow for the greatest design flexibility. The requirement that Type CMP-LP or CMR-LP cables meet the requirements in 800.179 allows for AHJs to make Code-based decisions on the suitability of cable. Type CMP-LP or CMR-LP cables cannot withstand continuous flexing events and are not suitable as components within elevator traveling cables.
■ Its Effect: As elevator cars get “smarter,” it is important that the NEC and the electrical professional remain current with technological changes. This change to 620.36 allows for maximum flexibility while maintaining safety.
Revision – 620.51(A) Type. Ex. No. 2
Stairway Chair Lift
■ What Changed: Exception 2 revised clarifying situations where the cord-and plug connection of a stairway chair lift is allowed. This includes new language concerning installations where a stairway chairlift is supplied by batteries as the primary source. This exception recognizes a plug-and-cord connection as an acceptable disconnecting means where a chair lift uses batteries as its primary power source. This change allows for safety to be maintained while recognizing new conveyance technology.
■ Its Effect: The new exception provides guidance to the electrical professional when installations of this type are encountered. It eases Code-compliance issues faced by installers and inspectors for smaller buildings utilizing chair lift systems.
Revision – 625.6
Listed (Electric Vehicle Power Transfer)
■ What Changed: Clarification added to which electric vehicle equipment involved in electric vehicle power transfer systems should be listed in Section 625.6. There was confusion among electrical professionals as to which charging/ transfer equipment was required to be listed. The xxx.06 section has become the location associated with listing requirements in many articles of the NEC. Clarification has been made that specifies which equipment involved with charging, power export, or bidirectional current flow must be listed.
■ Its Effect: This change removes confusion by stating plainly NEC listing requirements involved in this type of equipment. It will aid in achieving safety and simplify decisions for electrical professionals.
Revision – 625.44(A)
Portable Equipment
■ What Changed: 60-ampere receptacles were added to the list of permitted receptacle amperages for portable electric vehicle supply equipment (EVSE) in Section 625.44(A). In the interest of reducing charging time, some EV manufacturers have specified larger capacity circuits for charging their vehicles. This change will now recognize single-phase receptacles of up to 125/250 volts and 60 amperes for portable charging equipment. This 60-ampere rating was also accepted for fastened-in-place electric vehicle supply equipment (EVSE) and wireless power transfer equipment (WPTE).
■ Its Effect: The revision at 625.44(A) allows electrical professionals to install larger branch circuits and overcurrent protective devices for electric vehicle charging. It will allow AHJs to evaluate and consider approvals for installations not previously allowed by the Code.
New – 625.49
Island Mode
■ What Changed: New Section 625.49 was created stating that electric vehicle power export equipment (EVPE) and bidirectional electric vehicle supply equipment (EVSE) are permitted to be a part of interconnected power systems operating in an island mode condition. Island mode is a condition involving power production equipment or microgrids. It allows energy to be supplied to loads that have been disconnected from an electric power production and distribution network or other primary power sources. The section further clarifies that this EVPE and EVSE equipment can be a source for these types of systems.
■ Its Effect: This new language clarifies for electrical professionals any misconceptions that might have existed concerning electric vehicle power export equipment (EVPE) and bidirectional electric vehicle supply equipment (EVSE). This technology is advancing and becoming more and more prevalent. Electrical professionals need to understand how they are intended to interact with the interconnected power system(s).
New – 630.8
Ground-Fault Circuit-Interrupter Protection for Personnel (Electric Welders)
■ What Changed: New Section 630.8 was created requiring ground-fault circuit-interrupter (GFCI) protection for personnel involved with electric welder applications. The use of this equipment and associated equipment expose these users to electrical risk. This change is not for the welder receptacle but rather for other receptacles within the area where the welder is being used, and other tools might be connected.
■ Its Effect: The requirement is to expand GFCI protection for individuals using hand tools in these environments. The electrical professional will need to be aware of the 125-volt, 15- and 20-ampere receptacles supplied by single-phase branch circuits rated 150 volts or less to ground that electrical hand tools or portable lighting equipment can be connected and utilized around welding equipment. These receptacles will require GFCI protection to be installed to protect the end-user.
Revision – 646.19
Entrance to and Egress from Working Space
■ What Changed: The revision of Section 646.19 specifies the requirements for egress doors located in modular data centers. Previous Code editions did not clearly specify egress door opening requirements when the door is not of the “swinging” type. This change will include width and height requirements where the egress opening may be a sliding or “barn door” type. This ensures that personnel entering the working space will be able to exit in the event of an emergency and prevent injuries or deaths.
■ Its Effect: This change removes a gap in previous Code requirements concerning egress from modular data centers. Electrical professionals and other personnel will now be assured of sufficient egress space regardless of installed door type. It will also raise the level of safety for maintenance workers working within this environment.
Revision – 670.1
Scope. (Industrial Machinery)
■ What Changed: Section 670.1 revised to now include overvoltage protection for supply conductors for industrial machinery. Informational Note No. 1 was added to point the user to NFPA 79, Electrical Standard for Industrial Machinery, for machine construction guidance. Informational Notes No. 2 and No. 3 were added to clarify clearance requirements.
■ Its Effect: AHJs will now have a more effective tool in mandating safety requirements regarding industrial machines. Electrical professionals will have a clearer path to achieve safety for machine operators/maintenance personnel.
Reorganization – Article 680
Swimming Pools, Fountains, and Similar Installations
■ What Changed: Article 680 underwent a major reorganization to improve usability and compliance with the NEC Style Manual. Several sections were identified as redundant or unnecessary. Many provisions previously included in Article 680 repeated general requirements from Chapters 1-4. Structure requirements in 90.3 indicate that requirements in Chapters 5, 6, and 7 supplements or modify the general requirements in Chapters 1-4. Significant work was done to better comply with 90.3.
■ Its Effect: While many industry individuals work significantly with “special occupancies, equipment, and conditions” and like to have every requirement they need in the same location as the supplemental or modified requirements, that concept results in a lack of uniformity from an organizational standpoint. These changes are one step to achieve better compliance with the NEC Style Manual providing better usability by the electrical professional.
Revision – 680.5
Ground-Fault Circuit-Interrupter Protection (GFCI) and Special Purpose Ground-Fault Circuit-Interrupter (SPGFCI) Protection
■ What Changed: Text at Section 680.5 has been revised and subdivided to address ground-fault circuit-interrupter (GFCI) protection. It introduces special purpose ground-fault circuit-interrupter (SPGFCI) protection, a new GFCI protection requirement for circuits above 150 volts to ground, but not more than 480 volts phase-to-phase, single- or three-phase. The protection for higher voltage circuits shall not exceed 20-mA ground-fault trip current. GFCI protection has been required, and the equipment to be readily available for pool installations at typical single-family dwellings and smaller commercial facilities (120/240, single-phase and 208Y/120, single- and three-phase installations). However, some larger installations utilize electrical systems that operate outside the volage system parameters of Class A GFCI protection. This change is directed at providing protection at those installations.
■ Its Effect: Industry members must learn and understand how Class C, D, and E GFCI equipment functions. The NEC text indicates it protects at values not to exceed 20 mA. The protection is dependent on branch circuit conditions correlating with installation limitations (for size and/or continuity of the equipment grounding conductor or possibly double insulation, etc.) included in the certification. Class A GFCI can be verified if the protective device is installed on the supply side of the protected circuit or equipment. This provision applies in various parts and sections of Article 680. While this change expands protection to additional systems and equipment, it will require additional training and understanding.
Revision – 680.9(A)
Power
■ What Changed: Section 680.9(A) received clarification that open overhead wiring in raceways is not subject to the clearance requirements in Table 680.9(A) and Figure 680.9(A). A literal reading of the previous text had the potential to be a problem for overhead wiring in raceways in ceilings of indoor pool installations. This change clarifies the clearance requirements were focused on outdoor open wiring type installations.
■ Its Effect: This change provides improved text for the electrical professional to address potential hazards without restrictions that have little impact on electrical safety.
Revision – 680.10
Electric Pool Water Heaters Incorporating Resistive Heating Elements
and Electrically Powered Swimming Pool Heat Pumps and Chillers
■ What Changed: The text has been revised in Section 680.10 and subdivided to include provisions for pool water temperature conditioning equipment that incorporates technology other than resistance heating. Historically, 680.10 addressed the installation of electric resistance heating equipment to improve water temperature in pools. That heating equipment has been in use for many years. More recently, the installation of heat pump and chiller equipment has been used to heat or cool water temperature. This change recognizes this type of installation and provides requirements to size circuits and protective devices.
■ Its Effect: This expansion of 680.10 provides designers, installers, and AHJs with clear NEC requirements to address equipment utilizing technology not used historically in pool installations.
Revision – 680.21(D)
Pool Pump Motor Replacement
■ What Changed: The revisions at 680.21(D) expand the requirement to provide ground-fault circuit-interrupter (GFCI) protection for replaced pool pump motors and also include those that are repaired, but not replaced. GFCI protection enhances safety for pool users and workers maintaining pool equipment. Previous text only required GFCI protection for installations where the pump motor was replaced. This change adds an additional condition where GFCI protection must be provided.
■ Its Effect: Pool motor repair projects must now incorporate the addition of GFCI protection. That includes the repair of motors that operate on systems that exceed Class A GFCI limitations. Those must be addressed by special purpose groundfault circuit-interrupter (SPGFCI) protection. The electrical professional, facility owner, and pool maintenance personnel will need to be aware of these important safety requirements.
Revision – 680.12
Equipment Rooms, Vaults, and Pits
■ What Changed: Text at Section 680.12 has been revised and subdivided to require equipment rooms, vaults, or pits with equipment to have drainage or be suitable for submersion in first-level subdivision A. New first-level subdivision B requires a 125-volt, 15-or 20-ampere receptacle and requires any receptacle in the space rated 150 volts or less to be ground-fault circuit-interrupter (GFCI) protected. The revision to this section includes multiple concepts. One concept addresses a concern related to the risk of water rising over electrical equipment. Another concept mandates a receptacle for maintenance. The last concept addresses shock protection for personnel for any receptacle installed.
■ Its Effect: This requires the electrical professional to correlate drainage or equipment purchases to comply with 680.12(A). Additionally, the electrical industry will be required to provide a general-purpose receptacle and provide GFCI protection for all receptacles.
Revision – 680.23(B)(2)(a)
Forming Shell. (Metal Conduit)
■ What Changed: Rigid metal conduit extending directly to wet niche luminaires in forming shells of pools must now be listed red brass or listed stainless steel. Previous text required metal conduit for this application to be listed and identified. That text did not clearly describe the purpose of the “identification”. The revised text makes it clear the requirement limits the materials permitted for this application. UL 6A, Standard for Safety Electrical Rigid Metal Conduit- Aluminum, Red Brass and Stainless Steel, includes the certification requirements for the permitted metal conduit products.
■ Its Effect: This will benefit the electrical professional and bring clarity to this requirement in the Code. Many installations utilize nonmetallic conduit for this application as permitted by 680.23(B)(2)(b), however, metal conduit is the product of choice in some areas.
Revision – 680.32
Ground-Fault Circuit-Interrupter (GFCI) and Special Purpose Ground-Fault Circuit-Interrupter (SPGFCI) Protection.
■ What Changed: Title and text of Section 680.32 was revised to indicate that both ground-fault circuit interrupter (GFCI) and special-purpose ground-fault circuit interrupter (SPGFCI) requirements are covered in this section and added a reference back to 680.5(B) and (C). This more accurately depicts the requirements covered in this section
■ Its Effect: This change provides the electrical professional with more options for providing electrical shock protection to the user of this type of equipment.
Revision – 680.41(A)
Emergency Switch for Spas and Hot Tubs
■ What Changed: The emergency switch requirement was clarified at one-family dwellings for hot tub and spa installations in Section 680.41(A).
■ Why it happened: There was confusion about emergency switch requirements for hot tubs and spas at single-family dwellings. Emergency switch requirements do not apply for indoor or outdoor hot tub or spa installations at single-family dwellings.
■ Its Effect: This revision makes requirements easier to understand for the electrical professional. In the past, some AHJs have interpreted the Code to require emergency shutoff devices at single-family dwelling locations. This change should alleviate this misunderstanding.
Revision – 680.44
Ground-Fault Circuit-Interrupter (GFCI) and Special Purpose Ground-Fault Circuit-Interrupter (SPGFCI) Protection
■ What Changed: Section 680.44 was revised to indicate that both GFCI and SPGFCI requirements are addressed for spa and hot tub installations. This change will more accurately depict the requirements covered in this section as it applies to GFCI and SPGFCI requirements and aligns with the new definition of “SPGFCI” in Article 100. The wording “listed, labeled, and identified” in (B) was changed to “listed“ for clarity of the requirement
■ Its Effect: This change provides the electrical professional with more options for providing electrical shock protection to the user of this type of equipment. Using the word “listed” helps the electrical professional understand equipment requirements for this location.
New – 680.54(C)
Equipotential Bonding of Splash Pads
■ What Changed: New 680.54(C) was added to address bonding requirements for splash pads. Splash pads were introduced to the NEC in 2020 as a type of fountain. This change provides additional information to assist with the identification of the splash pad boundary. Many splash pads are constructed such that the area outside the splash pa perimeter is also concrete, but the equipotential bonding of the conductive splash pad (pool) shell terminates at some point. This change is an effort to identify that termination point. This will help assure the electrical safety of the user of this equipment.
■ Its Effect: Electrical industry members must seek information and understanding of splash pad structure from the splash pad (pool) designer. Proper communication of this requirement will significantly impact the installation and inspection approval of the bonding provisions.
Deletion – Article 690
Solar Photovoltaic (PV) Systems
■ What Changed: The use of the term “PV output circuit” has been removed throughout Article 690. All circuits and conductors will be considered a PV source, whether individual or combined. The definition of PV circuits also changed to properly align with these changes. Existing language at times created confusion in the field, and the use of the term “output circuit” was not necessary.
■ Its Effect: These changes will enhance the applicability and usability of the Code for the electrical professional.
New – 690.1
Figure Informational Note Figure 690.1(a), (b), (c)
■ What Changed: New simplified illustrations added to Section 690.1 identifying typical PV system dc components and conductors using new or revised definitions. The previous illustrations included non-PV elements and did not reflect current usage. The previous three figures were combined into one figure for simplicity.
■ Its Effect: The new illustrations will provide a better understanding
of the PV system dc circuit conductors and elements for NEC users.
New – 690.4(G)
PV Equipment Floating on Bodies of Water
■ What Changed: A new subdivision (G) was added to 690.4. This change recognizes the installation of floating PV arrays over a body of water and the additional product identification requirements. PV system arrays of modules that float on water are becoming more common, and the requirements for the equipment must be identified. The unique location requires the use of electrical devices and equipment that are suited for the environment. The new text will provide minimum requirements applicable to these types of projects. The new informational note provides additional clarity regarding the unusual conditions that exist for PV arrays located on water.
■ Its Effect: Without the benefit of a specific product safety standard for floating arrays, the CMP needed to address requirements through NEC language. Equipment must be identified for the purpose, and wiring methods must allow for movement.
Revision – 690.9(D)
Transformers
■ What Changed: Language was revised in Section 690.9(D), providing a pointer to 705.30(F), where specific requirements applicable to interconnected systems are addressed. Since Article 690 does not provide the requirements for interconnected systems, the language addressing sources on both sides was deleted, and a pointer to 705.30(F) was provided. The language of 705.30(F) addresses the requirements for transformers used with interconnected electric power production sources, where there may be sources of supply connected to both the primary and secondary windings of the transformer. The word “Power” was removed from the title to correlate with Article 450.
■ Its Effect: Clarity and consistency for identification of transformer primary and secondary circuits and resulting overcurrent protection rules are simplified for designers, installers, and inspectors.
Revision – 690.12
Exception No. 2 & Informational Note
■ What Changed: Rapid shutdown requirements for structures where firefighters will not need to access the roof was removed. The rapid shutdown requirements were created to provide a greater degree of safety for rooftop firefighting operations. The previous language included a limited exception for buildings associated with ground-mounted arrays but did not address other types of structures. The new Exception 2 extends the exception to include carports and other non-enclosed detached structures where firefighting operations do not require roof access.
■ Its Effect: The specific identification of structures exempt from rapid shutdown requirements will provide much-needed clarity for designers, installers, and inspectors.
Revision – 690.12(B)(2)
Inside the Array Boundary
■ What Changed: Two options were revised in Section 690.12(B)(2) for rapid shutdown compliance within the array boundary. The previous option (3) was eliminated. The new UL 3741, PV Hazard Control, standard was created to better address the specific electrical hazards for firefighters when responding to a rooftop incident that includes a PV system. The first option for compliance within the array boundary is through the use of a listed PV shock hazard control system installed in accordance with the manufacturer’s installation instructions. The second option requires the reduction of the voltage within the array to a maximum of 80 volts dc or less within 30 seconds.
■ Its Effect: Designers, installers, and inspectors will have two options for compliance within the array. This will help clarify understanding and compliance for this important safety requirement.
Revision – 690.15
Disconnecting Means for Isolating Photovoltaic Equipment
■ What Changed: Section 690.15 was rearranged with some grammatical changes. A requirement for an equipment disconnecting means to be within 10 feet of the equipment to now be within sight was also modified. The change goes toward the reorganization of 690.15(C) and (D) in the 2020 NEC. Section 690.15(A) now refers to 690.15(C) for an equipment disconnect and requires the disconnecting means to be within sight and within 10 feet of the equipment or be capable of being lockable in accordance with 110.25 for the 2023 code cycle. Changes in the reorganizing of 690.15(C) do not mandate the 10-foot requirements provided the disconnect complies with 110.25. Also, it only applies to disconnecting means and not isolating devices.
■ Its Effect: Instead of having a prescriptive distance of 10 feet, there will be a more liberal requirement of “in sight of ” which may lead to some enforcement discrepancies. See 110.29 for requirements for “In Sight From (Within Sight From, Within Sight).”
Revision – 690.31(B)
Identification and Grouping. (1) Conductors of Different Systems. Exception List Item (2)
■ What Changed: Section 690.31(B) was revised and a new list item (1), Conductors of Different Systems, was added while the previous text in that location was moved to list item (2), Identification. The text revisions provide conditions where PV dc circuits and inverter output circuits can now be installed in the same junction box, pull box or wireway provided they are identified, grouped, and separated in accordance with 690.31 (B)(2) and (B)(3). This change was made to provide relief where inverters are installed in conjunction with a wireway or box.
■ Its Effect: The updated language will grant relief to the electrical professional on installation practices while maintaining separation between dc circuits and ac circuits in the enclosures referenced. Conductors of different systems are still not permitted to share a common raceway.
Revision – 690.31(B)(1)
Conductors of Different Systems. – Exception
■ What Changed: Exception revised to permit the dc and ac conductors of a PV system to be located within the same enclosure where all the conductors are insulated for the highest voltage present and grouped appropriately. The previous language prohibited an inverter’s dc and ac conductors from being located within the same field-installed enclosure without a divider. Because the dc and ac conductors will all terminate within the inverter, there is a benefit from a workmanship perspective to permit these conductors within the associated wireway enclosure.
■ Its Effect: This change will simplify the routing of dc and ac PV system conductors to inverters for the installer. The revised format and new exception #2 will permit the common field installation of a wireway beneath an inverter that contains dc and ac conductors insulated for the highest voltage present. The previous rule required a divider to be installed.
Relocation – 700.2, 701.2, 702.2, and 708.2
Reconditioned Equipment
■ What Changed: Clarification that the reconditioning of transfer switches is not permitted for emergency systems, legally required standby systems, optional standby systems, and critical operations power systems (COPS).
■ Its Effect: This change helps electrical professionals with what equipment can and cannot be reconditioned. Stating this in these articles enhances the usability of the Code and provides definite direction concerning these items.
New / Revision – 700.3(F)
List items (4), (6), and (7).
■ What Changed: Revised subdivision (F) to include revised list item (4) requiring listing, added a new (6) for the permanent connection point and routing requirements for cables, and a new (7) requiring a label to be field applied at the permanent connection point. There have been life safety concerns experienced or expressed when alternate power sources are being maintained or repaired.
■ Its Effect: This change will give clarification and guidance to the electrical professional, helping to reduce inaccurate labeling at the connection point and reduce cable damage and building egress concerns. The installer and inspector must work together to ensure a safe system is in place during the repair or maintenance of alternate power sources.
Revision – 700.5(D)
Redundant Transfer Equipment
■ What Changed: The structure of 700.5 concerning transfer equipment now mirrors the subdivisions for transfer equipment found in Article 708.24. New subdivision (D) describes the functionality needed when a single feeder supplies emergency loads. Previously the language described how to do this based on a single product available on the market. There are multiple ways to meet the requirements safely and reliably and ensure continuity of power when a single feeder supplies an emergency load.
■ Its Effect: This change will improve consistency between code articles and enhance useability for the electrical professional. It also allows the NEC not to be seen as specifying a specific brand of electrical equipment. The previous text could prove problematic and burdensome for the AHJ and installers.
New – 700.11(C)
Wiring, Class 2 Powered Emergency Lighting Systems
■ What Changed: New requirements added for the separation of Class 2 circuits designated as emergency or nonemergency circuits in Section 700.11(C). The separation of Class 2 circuits used for different purposes was not defined in the previous edition, so 700.11(C) was created to define acceptable methods clearly.
■ Its Effect: Separation of circuits allows the installer and inspector to readily identify by bundled Class 2 circuits from emergency and nonemergency circuits or by bundling or barrier separation. This change provides additional integrity to the emergency lighting system in so far as it prevents collateral damage during maintenance activities.
New – 700.12(C)
Supply Duration
■ What Changed: An informational note was added to reference classification information for emergency power supply systems (EPSS) used with emergency systems. It will clarify that all Emergency and Standby Power Systems (EPSS) now require a minimum of not less than two hours of fuel for operation from the previous 1 ½ hours. This change will ensure all EPSS have the same required rating and capacity to supply and maintain the total load for a minimum period of 2 hours without being refueled or recharged.
■ Its Effect: This change should bring clarity to the electrical professionals for the requirements for EPSS installations used with emergency systems. The change in the Standard for Emergency and Standby Power Systems (EPSS) require consistent hours of operation regardless of the type of system installed. Testing these different EPSS installations will also become consistent as required in NFPA 110.
Revision – 700.12(E) & 701.12(E)
Stored-Energy Power Supply Systems (SEPSS)
■ What Changed: The title of Sections 700.12(E) and 701.12(E) have been changed from “Uninterruptible Power Supplies” to “Stored-Energy Power Supply Systems (SEPSS).” These revisions expand what will be encountered for the newly defined stored-energy power supply systems (SEPSS). This includes items such as an uninterruptible power supply (UPS), fuel cell systems, energy storage systems (ESS), storage batteries for DC loads, and any “other” option complying with 700.12 since these technologies may not represent an all-inclusive list.
■ Its Effect: This change recognizes more options that are now available to the electrical professional for stored-energy power supply system (SEPSS) installations. The professionals will need to be aware that new options exist and understand the guidelines associated with their installation.
Revision – 700.12(G)
Microgrid Systems
■ What Changed: The existing 700.12(G) was moved into 700.12(E) and replaced with a new 700.12(G) titled Microgrid Systems. Existing Section 700.12(G) was replaced, recognizing there are different types of microgrids, in addition to any that might be categorized as dc only.
■ Its Effect: This change provides additional guidance to electrical professionals when designing, installing, or inspecting on-site sources that have been designated as emergency sources connected to microgrid systems.
Revision – 701.4(C)
Load Management
■ What Changed: Modifications made to the title of Section 701.4(C), which now simply addresses load management requirements. “Peak load shaving” has been removed from the title. Parallel source requirements are addressed in 701.4(D), titled Parallel Operation.
■ Its Effect: This new section is being added to aid electrical professionals in more easily identifying the requirements unique to power sources used in legally required systems that can operate in parallel with a normal source.
New – 701.4(D)
Parallel Operation
■ What Changed: Language added that now identifies the two different types of parallel operation, normal and alternate sources, of legally required systems in new Section 701.4(D). Normal Source was added at 701.4(D)(1) to provide the requirements of interconnected electric power production sources found in Article 705. These are to be maintained at all times and also comply with Part I and II of Article 705. Additionally, the signaling of system malfunction per 701.6(A) regardless of any failure within the operation of legally required standby system(s) that would compromise the capacity requirements now notifies the user of the operating system(s) distress.
■ Its Effect: The electrical installer and the inspector are provided a clear direction of which system(s) is effectively operational and any reduction of load capacity causing system(s) malfunction. The added changes ensure the required standby load is maintained at all times as well as while keeping the economy in mind, using the alternate source(s) during their most efficient or peak production times could be considered.
New – 701.10
Wiring Legally Required Standby Systems
■ What Changed: A new first-level subdivision (B) was added and new figure informational notes concerning wiring requirements for legally required standby systems to Section 701.10. This addition provides a correlation with 700.10(B)(5)(b). These systems are installed to supply legally required loads, such as heating and refrigeration systems, communications systems, ventilation, and smoke removal systems, sewage disposal, lighting systems, and industrial processes. If these loads are interrupted due to a failure of the normal
building service, it could create hazards or hamper first responder operations.
■ Its Effect: The electrical professional now has additional guidance and clarification for wiring and overcurrent protection options associated with a feeder(s) for legally required systems. Understanding these requirements is critical to the safety of these very important systems.
New – 701.12(C)
Supply Duration
■ What Changed: An informational note added at Section 701.12(C) to reference classification information for emergency power supply systems (EPSS) used with legally required standby systems. This will clarify that all Emergency and Standby Power Systems (EPSS) now require a minimum of not less than 2 hours of fuel for operation from the previous 1 ½ hours. This update will ensure all EPSS have the same required rating and capacity to supply and maintain the total load for a minimum period of 2 hours without being refueled or recharged.
■ Its Effect: This change should bring clarity to the electrical professionals for the requirements for EPSS installations with legally required standby systems. The change in the Standard for Emergency and Standby Power Systems (EPSS) require consistent hours of operation regardless of the type of system installed. Testing these different EPSS installations will also become consistent as required in NFPA 110.
Revision – 705.11
Source Connections to a Service
■ What Changed: Section 705.11 has been completely revised and applies to systems interconnected with a new or existing utility service. None of the revised 705.11 language provides any new requirements. The entire section is now a restatement of existing Article 230 and Article 250 rules.
■ Its Effect: This change is intended to provide the electrical professional with enhanced usability and clarity regarding the basic applicable requirements of NEC Chapters 1–4.
Relocation – 705.13
Energy Management Systems (EMS)
■ What Changed: Most of the requirements that were located in Section 705.13 have been deleted. The requirements previously located in 705.13 were relocated to Article 750 entitled Energy Management Systems.
■ Its Effect: This should have a positive impact on the electrical industry as the requirements are all now in one location. It should also aid in usability and greater understanding by the electrical professional concerning these requirements.
Deletion – 705.20
Source Disconnecting Means
■ What Changed: The requirement for enclosure covers in Section 705.20 requiring a tool to open or be locked has been deleted. This action was taken due to the language that exists at 404.30. This information is applicable throughout the NEC and will continue to protect unqualified people from accessing the equipment and becoming injured.
■ Its Effect: This change will add clarity for the electrical professional as it will remove a redundant requirement. The information located at Section 404.30, Switch Enclosures with Doors, will provide the necessary information for these installations.
New – 705.30(F)
Transformers
■ What Changed: New language has been added at Section 705.30(F) to address transformer requirements for interconnected systems. The revised language now correlates with the transformer installation rules of Articles 240, 450, and the transformer product safety standard. This change was necessary to ensure that proper overcurrent protection is provided for transformer secondary conductors where sources of supply are connected to both sides.
■ Its Effect: Clarity and consistency for identifying transformer primary and secondary circuits and resulting overcurrent protection rules in interconnected systems are simplified for designers, installers, and inspectors.
Revision – 705.50
System Operation
■ What Changed: The language describing the operational modes of a Microgrid in Section 705.50 was rewritten to clearly state that a microgrid can operate in parallel with other systems or in island mode. This will help with clarification and to make sure the language is consistent with other NEC sections. A new Informational Note has been added to address health care facilities that have plans for microgrid installations.
■ Its Effect: It will add clarity for the electrical professional to the operational functionality of a microgrid.
New – 706.7
Commissioning and Maintenance (Energy Storage Systems)
■ What Changed: Commissioning requirements have been added, which will now align with requirements found in Chapter 6 of NFPA 855-2020, Standard for the Installation of Stationary Energy Storage Systems. The existing text has been revised, adding commissioning requirements for energy storage systems in a new subdivision (A). The existing requirements for maintenance of these systems were moved into the new (B).
■ Its Effect: These additions will require commissioning of the energy storage systems upon installation for other than one- and two-family dwellings installations. The electrical professional will need to provide necessary maintenance in accordance with manufacturer requirements or other industry standards. It assures the energy storage system will operate properly and in a safe condition.
New – Article 722
Cables for Power-Limited Circuits, Fault-Managed Power (Class 4) Circuits
■ What Changed: A new Article 722 was created for the general requirements for cables used with power-limited circuits and fault-managed power (Class 4) circuits installations. Wiring requirements for these cables were located throughout Chapter 7 of the NEC, making it hard to find at times. With these requirements relocated to one location (the new Article 722), it is anticipated the user of the Code will have an easier time finding the requirements.
■ Its Effect: There are concerns that installations and inspections of work covered in Chapter 7 are not done to the level you would find for installations covered by Chapters 1-4. This change is intended to make it easier for the electrical professional to find requirements, aiding in installation and enforcement.
Revision – 725.144
Bundling of Cables Transmitting Power and Data
■ What Changed: The words “4-Pair” were removed from the title of Section 725.144 and added it to the title subdivision (A), where it was applicable to the types of cables discussed. This change clarifies that 725.144 applies to any pair of cables and that only subdivision (A) and Table 725.144 apply to 4-pair cables. Subdivision (B) covers cables of any pair count and requires an “LP” listing. See UL 13, Standard for Safety Power-Limited Circuit Cables, that does not limit rating to 4-pair cables.
■ Its Effect: This change will help both installers and inspectors by clarifying the requirements for 4-pair cables and other cables. This change also provides a possible placeholder for future requirements concerning single-pair ethernet cables.
New – Article 726
Class 4 (CL4) Power Systems
■ What Changed: A new Article 726 was created for fault-managed power (FMP) systems in occupancies other than dwelling units. There have been over 1,000 installations of “Digital Electricity” in the United States, mostly at stadiums where large numbers of people gather. A failure in this environment could be disastrous, causing needless loss of life.
■ Its Effect: Class 4 systems have ground-fault circuit-interrupter (GFCI) equivalent protection (line to ground) while also introducing similar protection line to line. This allows for installations that do not require raceway systems. The higher voltage associated with this technology leads to lower current. This allow the electrical professional to install smaller conductors when compared to 120-volt AC systems. This reduces the materials required for installs, leading to a ‘greener’ construction project. Class 4 systems allow power in the kW range to be delivered using wiring methods more like Class 2 and Class 3 methods, other than methods found in Chapter 3. Smaller systems allow for greater floor space for the building owners to use for other purposes. A Class 4 system is envisioned to enable smart building expansion while allowing the natural integration of grid power with renewable and battery sources.
Revision / Relocation – Article 760
Fire Alarm Systems
■ What Changed: Several sections throughout Article 760 were reworded, revised, relocated, or deleted. Hazardous (Classified) Location requirements were reworded and relocated to 760.12 to be consistent with Article 722. Some requirements applying to cables have been relocated to Article 722.
■ Why it happened: These changes were part of the consolidation efforts towards requirements found throughout the NEC and moved into new Article 722. The end goal was greater useability.
■ Its Effect: The new requirements at 760.12 make it clear that these specialty cables are not exempt from requirements for Hazardous (Classified) Locations. The reference to the full articles has changed to specific section references to comply with the NEC Style Manual.
Relocation – 800.179
Wires and Cables
■ What Changed: Hybrid power and communications cable general requirements were moved to Article 800 with the other communication cable types. This revision revises the title from “Communications Wires and Cables” to “Wires and Cables” to avoid confusion and also moves the listing and marking requirements to this article. This section has general listing requirements for all cables in Chapter 8. The revised text clarifies that all wires and cables, except CATV-type cables, are required to have a minimum voltage rating of 300 volts.
■ Its Effect: The changes add usability to the NEC and increase safety for electrical systems. It simplifies the listing and marking requirements for enhanced usability by the electrical professional.
Relocation – 805.170
Protectors
■ What Changed: Communication equipment listing requirements were moved to Article 800 leaving two subdivisions (A) and (B) for primary and secondary protectors.
■ Its Effect: These changes will assist users of the Code by specifying these protective devices to be listed. It will help assure the safety of communication systems.
Revision – 840.160
Powering Circuits
■ What Changed: The reference from Section 725.154(A) was changed to Section 722.135(E) as cable substitution, and installation requirements are now in Article 722.
■ Its Effect: This revision makes Chapter 8 more user-friendly and helps avoid confusion while also moving the listing and marking requirements to Article 800. This section has general listing requirements for all cables referenced in Chapter 8.
New – Chapter 9 Table 13
Equipment Suitable for Hazardous (Classified) Locations
■ What Changed: New Table 13 created in Chapter 9 entitled Equipment Suitable for Hazardous (Classified) Locations. The text was deleted at 505.9(C)(2)(4) referencing Table 505.9 (C)(2)(4) with new text added to reference Chapter 9 Table 13. The requirements at 505.9(C)(2)(4) discuss zone equipment marking requirements. The new table provides a complete list of the types of protection for hazardous (classified) locations and improves the readability of 505.9(C)(2)(4).
■ Its Effect: This will assist the electrical industry by providing an improved list of equipment suitability for various locations. The new table and revisions will assist the designer, contractors, and the AHJ verify compliance with code and the manufacturer’s listing of the equipment that will be installed in a hazardous (classified) location for both zone and other classified locations.
Revision / New – Informative Annex A
Product Safety Standards
■ What Changed: The existing Informative Annex A was revised in order to reflect the current editions of safety standards and a new Table A.1(B) was added addressing product safety standards for conductors and equipment that do not have associated listing requirements.
■ Its Effect: Finding information quickly is important to the electrical professional as to applying the requirements of the NEC. These revisions and the addition of the new table allow the Code user to utilize Annex A with better clarity. This is an effort to increase access to relevant product and safety standards, thus increasing electrical safety.
New – Informative Annex E
Fire Resistance Construction
■ What Changed: E.2.1 for Type IV construction now includes traditional heavy timber construction and mass timber construction. These new changes provide alignment with the Model Building Codes.
■ Its Effect: Changes were required to address the addition of mass timber buildings to Type IV construction in the model building codes.